AgentSkillsCN

LCF5

LCF5

SKILL.md

LCF5 Energy Data Skill

Overview

LCF5 is a glasshouse facility with CHP engines, boilers, heat pumps, and CO2 systems. Energy data is stored at 15-minute intervals.

Primary Data Source

Use only dbo.qryEnergiData_15Min for all LCF5 queries.

Key Column: DateTimeLinkEnergy

  • Type: smalldatetime
  • Primary key / timestamp for all records
  • 15-minute intervals
  • Helper columns: Date, WeekComm (week commencing), YearMonth (format: YYYY-MM)

Column Naming Convention

Most columns follow the pattern: [Type]_[Asset]_[Agg|Diff]

  • _Agg = Cumulative/aggregate meter reading
  • _Diff = Interval consumption (use this for energy analysis)

Equipment Categories

CHP Engines (3 units: CHP1, CHP2, CHP3)

PrefixMeaningUnit
Gas_CHPxGas consumptionkWh
Gen_CHPxElectricity generatedkWh
Heat_CHPxHeat outputkWh
CO2_CHPxCO2 captured/producedkg

Boilers (2 units: Boiler1, Boiler2)

PrefixMeaningUnit
Gas_BoilerxGas consumptionkWh
Heat_BoilerxHeat outputkWh
Hrs_BoilerxRun hourshours

Heat Pumps (16 units: HP1–HP16)

PrefixMeaningUnit
Consum_HPxElectricity consumptionkWh

Grid Electricity

ColumnMeaning
Imp_EnergyCentreImport from grid
Exp_EnergyCentreExport to grid
Energy_Tariff2_ReverseSecondary tariff meter

Glasshouse Electricity

ColumnMeaning
Elec_GHNGlasshouse North consumption
Elec_GHSGlasshouse South consumption

Heat Distribution

ColumnMeaning
Heat_TotalTotal heat to site
Heat_RHIRHI-eligible heat
Heat_PumpHeat pump output
Heat_CO2Heat for CO2 system
Heat_DACDirect air capture heat
Heat_EffluentEffluent heat recovery
Heat_2_1Inter-zone heat transfer

CO2 System

ColumnMeaning
CO2_Chrg_Grow_KGCO2 charged to growing (kg)
CO2_Chrg_Grow_HRSCO2 charging run hours

Temperatures (point-in-time, not _Diff)

PrefixMeaning
Temp_HT01–HT10High-temperature sensors
Temp_LT01–LT10Low-temperature sensors
Temp_LTIn / Temp_LTOutLow-temp circuit in/out
Temp_GHGlasshouse temperature
Temp_Ambient_OSOutside ambient temperature
SetpP_GHN / SetpP_GHSGlasshouse setpoints (North/South)

Status Flags (bit columns)

ColumnMeaning
DaylightDaylight hours flag
UKPN_Zero_Export_ModeGrid export restriction active
Co2_LeadCO2 system leading
Thermal_LeadThermal demand leading
Facility_LeadFacility demand leading

Common Query Patterns

Daily totals

sql
SELECT Date, 
       SUM(Gen_CHP1_Diff + Gen_CHP2_Diff + Gen_CHP3_Diff) AS Total_CHP_Gen,
       SUM(Imp_EnergyCentre_Diff) AS Grid_Import
FROM dbo.qryEnergiData_15Min
WHERE Date >= '2024-01-01'
GROUP BY Date
ORDER BY Date

Weekly aggregation

sql
SELECT WeekComm,
       SUM(Heat_Total_Diff) AS Weekly_Heat
FROM dbo.qryEnergiData_15Min
GROUP BY WeekComm
ORDER BY WeekComm

CHP efficiency check

sql
SELECT Date,
       SUM(Gas_CHP1_Diff) AS Gas_In,
       SUM(Gen_CHP1_Diff) AS Elec_Out,
       SUM(Heat_CHP1_Diff) AS Heat_Out,
       (SUM(Gen_CHP1_Diff) + SUM(Heat_CHP1_Diff)) / NULLIF(SUM(Gas_CHP1_Diff), 0) * 100 AS Efficiency_Pct
FROM dbo.qryEnergiData_15Min
WHERE Date >= '2024-01-01'
GROUP BY Date

Notes

  • Always use _Diff columns for consumption/generation analysis
  • Use _Agg columns only when you need cumulative readings
  • Temperature columns are instantaneous readings (no _Diff)